Helping to light and power our homes and workplaces, Tratos’ Low Voltage (LV) cables are backed by a pedigree of proven experience and manufacturing capability.
(XLPE/SWA/LS0H)
POWER CABLES BASED ON IEC 60502-1
(XLPE/SWA/LS0H) - RTE4OM1FM1 - 0,6/1 kV Armoured fire performance power cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used where limited circuit integrity in the event of a fire is required.
Construction
Conductor: annealed copper wires according to cl. 2 of BS EN 60228
Fire barrier: mica/glass tape
Insulation: XLPE according to IEC 60502
Identification cores: black numbered
Assembly: concentric layers
Separation sheath: LS0H
Armour: galvanized steel wire
Outer sheath: LS0H
Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)
Standards
IEC 60502 Design and test guidelines
IEC 60332-1 Test for vertical flame spread, single cable
IEC 60332-3-22 Test for vertical flames spread bunched cables Cat A (if required) IEC 60331 Tests for electric cables under fire conditions - Circuit integrity IEC 60754 Determination of acid gas contentIEC 61034 Measurement of smoke density
(XLPE/LS0H)
POWER CABLES BASED ON IEC 60502-1
(XLPE/LS0H) - RTE4OM1 - 0,6/1 kV - Unarmoured fire performance power cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used where limited circuit integrity in the event of a fire is required.
Construction
Conductor: annealed copper wires according to cl. 2 of BS EN 60228
Fire barrier: mica/glass tape
Insulation: XLPE according to IEC 60502
Identification cores: black numbered
Assembly: concentric layers
Identification cores: black numbered
Assembly: concentric layers
Outer sheath: LS0H
Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)
Standards
(XLPE/SWA/PVC or XLPE/SWA/LS0H)
POWER CABLES BASED ON IEC 60502-1
(XLPE/SWA/PVC or XLPE/SWA/LS0H) - RE40RFR(M1) - 0,6/1 kV - Armoured power cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Identification cores: black numbered
Assembly: concentric layers
Fillers: non hygroscopic compound or LS0H non hygroscopic compound
Armour: galvanized steel wire
Sheath: PVC or LS0H
Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)
Standards
(XLPE/PVC or XLPE/LS0H)
POWER CABLES BASED ON IEC 60502-1
(XLPE/PVC or XLPE/LS0H) - RE40R(M1) - 0,6/1 kV - Unarmoured power cable for indoor installations in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Identification cores: black numbered
Assembly: concentric layers
Penetrant sheath: PVC or LS0H
Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
IEC 60332-3 C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties
IEC 61034 Low smoke emission
(XLPE/TratosCB®/PVC)
POWER cables
(XLPE/TratosCB®/PVC) - RE4OH5R4R 0,6/1 kV - multi-core - Multi-core cable for installation in and around process plants where hydrocarbons are present without using Lead.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228
Insulation: XLPE compound
Fillers: non hygroscopic compound
Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer
Sheath: PVC
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
(XLPE/TratosCB®/PVC)
POWER cables
(XLPE/TratosCB®/PVC) - RE4H5R4R 0,6/1 kV - single-core - Single core cable for installation in and around process plants where hydrocarbons are present without using Lead.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228
Insulation: XLPE compound
Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer
Sheath: PVC
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
(XLPE/Pb/SWA/PVC)
POWER cables
(XLPE/Pb/SWA/PVC) - RE4OLRFR 0,6/1 kV - multi-core - Multi-core, armoured, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Fillers: non hygroscopic compound
Metallic sheath: lead alloy
Separation sheath: PVC
Armour: galvanized steel wires
Sheath: PVC
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
(XLPE/Pb/AWA/PVC)
POWER cables
(XLPE/Pb/AWA/PVC) - RE4LRFR 0,6/1 kV - single core - Single core, non-magnetic armoured, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228
Insulation: XLPE compound according to IEC 60502
Metallic sheath: Lead alloy
Separation sheath: PVC
Armour: aluminium wires
Sheath: PVC
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
(XLPE/Pb/PVC)
POWER cables
(XLPE/Pb/PVC) - RE4OLR 0,6/1 kV - multi-core - Multi-core lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Fillers: non hygroscopic compound
Metallic sheath: lead alloy
Sheath: PVC
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
(XLPE/Pb/PVC)
POWER cables
(XLPE/Pb/PVC) - RE4LR 0,6/1 kV - single core - Single core lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Metallic sheath: lead alloy
Sheath: PVC
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
(XLPE/SWA/PVC or XLPE/SWA/LS0H)
POWER cables
(XLPE/SWA/PVC or XLPE/SWA/LS0H) - RE4OM1(R)FM1(R) 0,6/1 kV - multi-core - Multi-core armoured and sheathed cable for fixed installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants, indoor or outdoor locations.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Inner covering: non hygroscopic compound or LS0H non hygroscopic compound
Armour: galvanized steel wire
Sheath: PVC or LS0H
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
IEC 60332-3 C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(XLPE/PVC or XLPE/LS0H)
POWER cables
(XLPE/PVC or XLPE/LS0H) - RE4M1(R) 0,6/1 kV - multi-core - Multi-core sheathed cable for fixed installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound according to IEC 60502
Fillers: non hygroscopic compound or LS0H non hygroscopic compound
Sheath: PVC or LS0H
Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
BS EN 60228 Conductors
IEC 60332-1 Flame retardant
IEC 60332-3 C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties
IEC 61034 Low smoke emission
(XLPE/AWA/PVC or XLPE/AWA/LS0H)
POWER cables
(XLPE/AWA/PVC or XLPE/AWA/LS0H) - RE4M1FM1(R) 0,6/1 kV - single core - Single core, non-magnetic, armoured power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228
Insulation: XLPE compound according to IEC 60502
Bedding: non hygroscopic compound or LS0H non hygroscopic compound
Armour: aluminium wires
Sheath: PVC or LS0H
Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
BS EN 60228 Conductors
IEC 60332-1 Flame retardant
IEC 60332-3 C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(XLPE/PVC or XLPE/LS0H)
POWER cables
(XLPE/PVC or XLPE/LS0H) - RE4M1(R) 0,6/1 kV - single core - Single core sheathed cable for fixed installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228
Insulation: XLPE compound
Sheath: PVC or LS0H
Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)
Standards
IEC 60502-1 Design and tests guidelines
BS EN 60228 Conductors
IEC 60332-1 Flame retardant
IEC 60332-3 C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties
IEC 61034 Low smoke emission
(PVC) N07V-K - 0,45/0,75 kV
Earthing cables
Single core unsheathed cable for fixed protected installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants. Flexible, fine wire, conductor to aid installation.
Construction
Conductor: bare copper circular flexible, according to cl. 5 of BS EN 60228
Insulation: PVC compound
Marking: (Year of manufacture) + (serial number) + (Tratos cable type) + [(number of cores) × (cross-section)] + (rated voltage)
Standards
CENELEC HD 21 Design and tests guidelines
IEC 60228 Conductors
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60227/03 Design and tests guidelines
(PVC/SWA/PVC or XLPE/SWA/LS0H)
CONTROL cables BASED ON EN 50288-7
(PVC/SWA/PVC or XLPE/SWA/LS0H) - RE4HM1FM1(R) - 300/500V - Armoured multi-element metallic control cables for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.
Construction
Conductor: annealed copper wires according to cl. 2
Insulation: PVC or XLPE
Identification cores: black numbered
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Inner sheath: PVC or LS0H
Armour: galvanized steel wire comply with EN 10244 cl. D
Outer sheath: PVC or LS0H
Marking: (EN 50288-7) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
EN 50288-7 Design guidelines
EN 50290-2 Specification for insulation and sheath material
BS EN 60288
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PVC/PVC or XLPE/LS0H)
CONTROL cables BASED ON EN 50288-7
(PVC/PVC or XLPE/LS0H) - RE4OHM1(R) - 300/500V - Unarmoured multi-element metallic control cables for indoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.
Construction
Conductor: annealed copper wires according to cl. 2
Insulation: PVC or XLPE
Identification cores: black numbered
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Outer sheath: PVC or LS0H
Marking: (EN 50288-7) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
EN 50288-7 Design guidelines
EN 50290-2 Specification for insulation and sheath material
BS EN 60288
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PVC/SWA/PVC or XLPE/SWA/LS0H)
CONTROL CABLES BASED ON PAS 5308
(PVC/SWA/PVC or XLPE/SWA/LS0H) - (F)(R)OHRFR(M1) - 300/500V - Armoured power cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: annealed copper wires according to cl. 1 or 2 or 5 of BS EN 60228
Insulation: PVC or XLPE
Identification cores: see table 7 on page 10
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Bedding: PVC or LS0H
Armour: galvanized steel wire
Outer sheath: PVC or LS0H
Marking: (PAS 5308-1) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
PAS 5308-1 Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PVC/PVC or XLPE/LS0H)
CONTROL cables BASED ON PAS 5308
(PVC/PVC or XLPE/LS0H) - (F)(R)ROHR(M1) - 300/500V - Unarmoured control cable for indoor installations in the petroleum industry, chemical and petrochemical plants.
Construction
Conductor: annealed copper wires according to cl. 1 or 2 or 5
Insulation: PVC or XLPE
Identification cores: see table 7 on page 10
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Outer sheath: PVC or LS0H
Marking: (PAS 5308-1) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
PAS 5308-1 Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PE/SWA/PVC or XLPE/SWA/LS0H)
Thermocouple cables BASED ON EN 50288-7
(PE/SWA/PVC or XLPE/SWA/LS0H) - UE(X)HOHRFR(M1) - 300/500V - Armoured cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits in and around process plants.
Construction
Conductor: solid alloy
Insulation: polyethylene or XLPE
Pairs: twisted
Identification pairs: according to ANSI MC 96.1 or IEC 60584
Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Outer sheath: PVC or LS0H
Armour: galvanized steel wire
Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
EN 50288-7 Design guidelines
EN 50290-2 Specification for insulation and sheath material
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PE/PVC or XLPE/LS0H)
Thermocouple cables BASED ON EN 50288-7
(PE/PVC or XLPE/LS0H) - UE(X)HOHR(M1) - 300/500V - Unarmoured cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits in and around process plants.
Construction
Conductor: solid alloy
Insulation: polyethylene or XLPE
Pairs: twisted
Identification pairs: according to ANSI MC 96.1 or IEC 60584
Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Outer sheath: PVC or LS0H
Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
EN 50288-7 Design guidelines
EN 50290-2 Specification for insulation and sheath material
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PE/SWA/PVC or XLPE/SWA/LS0H)
Thermocouple cables BASED ON PAS 5308
(PE/SWA/PVC or XLPE/SWA/LS0H) - METAL - UEXHOHRFR(M1) - 300/500V - Armoured cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits in and around process plants.
Construction
Conductor: solid alloy conductor
Insulation: polyethene or XLPE
Pairs: twisted
Identification pairs: numbered pairs and colour code according to ANSI MC 96.1 or IEC 60584
Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Bedding: PVC or LSOH
Armour: galvanized steel wire
Outer sheath: PVC or LSOH
Marking: (PAS 5308-1) + (Thermocouple type) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
PAS 5308-1 Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PE/PVC or XLPE/LS0H)
Thermocouple cables BASED ON PAS 5308
(PE/PVC or XLPE/LS0H) - METAL - UEXHOHR - 300/500V - Unarmoured cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits in and around process plants.
Construction
Conductor: solid alloy conductor
Insulation: polyethene or XLPE
Pairs: twisted
Identification pairs: numbered pairs and colour code according to ANSI MC 96.1 or IEC 60584
Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Outer sheath: PVC or LSOH
Marking: (PAS 5308-1) + (Thermocouple type) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
PAS 5308-1 Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)
(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)
Instrumentation cables based on EN 50288-7
(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC) - RE4(X)HOHR(M1)FR(M1) - 300V or 500V - Armoured multi-element metallic instrumentation cables for indoor or outdoor use in analogue and digital communication and control where higher levels of screening than provided by collective screen is required. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.
Construction
Conductor: annealed copper wires according to cl. 2
Insulation: polyethylene or XLPE
Pairs: twisted
Identification pairs: see table 11 & 12 on page 12
Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Assembly: concentric layers
Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm
Inner sheath: PVC or LS0H
Armour: galvanized steel wire
Outer sheath: PVC or LS0H
Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)
Standards
EN 50288-7 Design guidelines
EN 50290-2 Specification for insulation and sheath material
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60754 Halogen free properties (only for LS0H)
IEC 61034 Low smoke emission (only for LS0H)